Independent report

Fire test report: MHCLG BS 8414 HPL

These reports are intended to establish how High-Pressure Laminate panels in combination with stone wool insulation behave in a fire.

Documents

Fire test report: MHCLG BS 8414 HPL

This file may not be suitable for users of assistive technology. Request an accessible format.

If you use assistive technology (such as a screen reader) and need a version of this document in a more accessible format, please email alternativeformats@communities.gov.uk. Please tell us what format you need. It will help us if you say what assistive technology you use.

BR 135 cladding systems classification report

This file may not be suitable for users of assistive technology. Request an accessible format.

If you use assistive technology (such as a screen reader) and need a version of this document in a more accessible format, please email alternativeformats@communities.gov.uk. Please tell us what format you need. It will help us if you say what assistive technology you use.

Details

These reports are commissioned by the Ministry of Housing, Communities and Local Government and are intended to establish how High Pressure Laminate panels in combination with stone wool insulation behave in a fire.

The test was carried out by the Fire Protection Association on 11 July 2019. The detailed design of the test has been reviewed by the Expert Panel. The system was selected to ensure that it is representative of the systems that are in common use.

Published 18 July 2019