Testing standards of adhesives: UK21/F013

Adopted EU recommendation FIRE-051. UK approved recommendationon the correct testing standards for adhesives for use in A, B and C class divisions.

Question

SOLAS Ch. II.2, Reg.5, 3.1.1 mentions that adhesives used in conjunction with insulation shall have low flame-spread characteristics.

According to the International Code for Application of Fire Test Procedures 2010 (2010 FTP Code), annex 1, Part 3, chapter 3.5.1.1 and MSC/Circ.1120 (SOLAS Ch. II-2 Part A, 3.10), adhesives used in the construction of “A”, “B” and “C” class divisions shall have low-flame spread characteristics.

Testing according to the 2010 FTP Code, Part 2 (Smoke and toxicity test) is not mentioned for adhesives (Ref. SOLAS Ch. II-2, Reg. 6).

Which testing is required for the approval of adhesives in “A”, “B” & “C” class divisions?

Recommendation

Adhesives used in the construction of “A”, “B” and “C” class divisions (not as surface materials) shall satisfy the requirement of the 2010 FTP Code, Part 5 (Test for surface flammability).

Testing according to the 2010 FTP Code, Part 2 (Smoke and toxicity test) is not required in this case. 

References

Items affected

  • UK/3.18e, Surface materials and floor coverings with low flame-spread characteristics: adhesives used in the construction of “A”, “B” and “C” class divisions.